Permit Number: T18CM06109
Parcel: 11706320C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM06109
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/07/2018 EHAMBLI1 ZONING REVIEW Approved
08/07/2018 EHAMBLI1 ENGINEERING REVIEW Passed
08/07/2018 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. Verify compliance with Tucson-Pima County Outdoor Lighting Code.
2. E12.1 Show the location of the fault-current node on the one-lind diagram.
3. Panel type refers to C.B. NOTE; which cannot be located on the plans.
4. E5.1 Circuit designation LA-18 is mislabeled on the subpanel schedule; please correct.
08/07/2018 MARTIN BROWN FIRE REVIEW Approved
08/07/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/07/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/10/2018 SVALENZ1 MECHANICAL-COMMERCIAL REVIEW Needs Review
08/10/2018 SVALENZ1 PLUMBING-COMMERCIAL REVIEW Needs Review
08/10/2018 SVALENZ1 WATER REVIEW Needs Review