Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T18CM06091
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/26/2019 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | The City of Tucson has adopted the 2018 International Codes and the 2017 NEC. Please revise the Structural Calculations to the 2018 IBC and 2017 NEC . IBC 107.2.1. |
| 05/17/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. 1. Provide for the Grounding Electrode system and details required per NEC 690.47A. 2. Provide a grounding detail for the racking system, PV panels, and steel structure as required per 690, part V, NEC. Ref; 2017 NEC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/05/2019 | AVAUGHN1 | APPROVAL SHELF | Completed |
| 06/05/2019 | AVAUGHN1 | OUT TO CUSTOMER | Completed |
| 06/05/2019 | AVAUGHN1 | REJECT SHELF | Completed |