Permit Number: T18CM06091
Parcel: 12504004A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM06091
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2019 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change The City of Tucson has adopted the 2018 International Codes and the 2017 NEC. Please revise the Structural Calculations to the 2018 IBC and 2017 NEC . IBC 107.2.1.
05/17/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
1. Provide for the Grounding Electrode system and details required per NEC 690.47A.
2. Provide a grounding detail for the racking system, PV panels, and steel structure as required per 690, part V, NEC.
Ref; 2017 NEC.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/05/2019 AVAUGHN1 APPROVAL SHELF Completed
06/05/2019 AVAUGHN1 OUT TO CUSTOMER Completed
06/05/2019 AVAUGHN1 REJECT SHELF Completed