Permit Number: T18CM06089
Parcel: 138244190

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM06089
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/09/2018 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change PLUMBING – COMMERCIAL
Regarding response to previous plumbing comment 1, please submit approval for amalgam separator from Regional Wastewater Reclamation Department (Industrial Waste).
11/09/2018 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change ELECTRICAL
Regarding response to previous electrical comment 1, please revise note 1 on detail 1/E101 “Refer to structural sheets for footing detail.” Ref. 2012 IBC 107.2.1.
Regarding response to previous building comment 3, required outdoor lighting information was not submitted in tabular form as requested. Per previous comment, “please submit outdoor lighting lumen calculations in accordance with the 2012 City of Tucson/Pima County Outdoor Lighting Code Table 401.1. Select a commercial lighting option for lighting area E3 and provide calculations in tabular form for allowable total lumens (fully shielded plus unshielded) and for total allowable unshielded lumens. The proposed total lumens and the proposed unshielded fixtures lumens shall match or be less than the allowable lumens. For each fixture indicate “fully shielded” or “unshielded”. Refer the definitions for each in the OLC. The photometric site plan on sheet E101 does not provide the information required” in a form that is easily reviewed.
11/09/2018 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Completed
11/09/2018 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change Reviewer: Chris Anderson, November 6, 2018
BUILDING – COMMERCIAL
Regarding response to previous building review comment 2: a) please remove the R Value Calculations on sheet G100. The COMcheck method used requires only that you plug in the insulation values. Values for other materials in the wall assembly are calculated internally by COMcheck, b) the values shown in the revised COMcheck are R-11.4 for cavity insulation and R-7.7 for the continuous insulation. What manufacturer/products provide insulation with these values? The building inspector will be looking for printed R-values on the installed product or to verify compliance.
Regarding response to previous building comment 3: the wall type legend on sheet A201 has been revised to show conflicting information. R-values for continuous and cavity insulation have been added under the pictogram that match what is now shown in the COMcheck (see building comment 1 above); however the written description to the right of the pictogram gives completely different R-values for continuous and cavity insulation.
On Wall Sections, sheets A602 and A603, revise keynote 4 to add R-value for 2 ½” cavity insulation. Ref. 2012 IBC 107.2.1. Regarding response to previous building comment 7: the R-value added for the 2 ½” stud cavities is shown as R-8. This does not match the COMcheck (see building note 2 above).
Please revise insulation values in the documents so that the wall types schedule, COMcheck and keynotes for wall sections match.
11/30/2018 JOHN VAN WINKLE ENGINEERING REVIEW Approved
11/30/2018 DAVID RIVERA ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: David Rivera for Steve Shields
Site Section Manager

PROJECT: 1979 W. Valencia Road
T18CM06089
Building Plan (2nd Review)

TRANSMITTAL DATE: November 30, 2018
Previous Comments still applicable. Once the commercial plans reviewers have approved the building plans zoning will also approve the plans.
1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The building plans have been reviewed for compliance with development package DP18-0139 and appear to meet all requirements but until the DP is approved and the following comments have been addressed Zoning cannot approve the building plan.

3. Until all other PDSD review agencies have approved the building plans zoning cannot approve.


If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956