Permit Number: T18CM06076
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM06076
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/06/2018 KELLY LEE ZONING REVIEW Approved
08/06/2018 KLEE1 ENGINEERING REVIEW Passed
08/07/2018 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Approved Approved per sec. IECC 405.5.1 ex. 8
08/07/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide kitchen exhaust per Sections 403.3 and 507.2.2, IMC 2012.
2. Verify that the proposed programmable thermostat complies with the requirements of Sections C403.2.4.1 through C403.2.4.3.3, IECC 2012
08/07/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/07/2018 MARTIN BROWN FIRE REVIEW Approved
08/07/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. See detail 3/A5.3 for the construction of the water heater support platform and coordinate with the architect.
2. Provide cleanouts for all horizontal drains, sized to match the pipe size.
3. Connect the mop sink, and the dump sink to the grease interceptor. Hand sinks that do not discharge to the grease interceptor shall be labeled to restrict their use to hand washing only. Reference: Section 1003.3, IPC 2012 as amended by the City of Tucson.
4. Beverage dispensers require the use of backflow preventers listed to ASSE 1022. Reference: Section 608.16.1, IPC 2012.
5. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012.
08/07/2018 ROBERT SHERRY WATER REVIEW Completed
08/07/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed