Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - RES
Permit Number - T18CM06071
Review Name: WALK THRU - RES
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/08/2018 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 08/08/2018 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 09/28/2018 | TWEIDEM1 | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | 1. The plans need to show the scope of work that is being done, provide description. 2. Label what the enclosed room is being used for. If it is being used for a bedroom, need to show a smoke detector. 3. Label the carport that will be enclosed on the site plan and floor plan. 4. The details that are highlighted are for reference only; details must be drawn out and submitted with the plan. 5. Need wall framing detail; show stud attachement to the foundation. 6. Provide a foundation detail of the footing under the new walls. 7. Show the attacment of the wall to the existing roof framing. |