Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T18CM06034
Parcel: 140260360

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM06034
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 6; Sheet A027-1BC; Occupancy Groups: Please indicate the correct Occupancy Group per the IBC Chapter 3.
2. Previous Comment 8; Sheet A027-1BC; Exiting Calculation: Please indicate the total exit width required, and the total exit width provided.
3. Previous Comment 14; Sheets A301-1BC and A301-1BD; Key Notes: Notes 1, 2, and 3 were not located. Please verify.
4. General: Please provide written responses to all review comments.
09/17/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change As per the previous electrical plan review, it was requested to assign a branch circuit and panel for the lighting and provide correlation with the panel schedule.
The room numbers shown in the panel schedules still do not correlate with actual room numbers shown on the architectural plans. For clarification, please show the room numbers on the electrical floor plans.
Ref; 2012 IBC 107.2.1, 2011 NEC art 408.4