Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM06034
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/14/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Previous Comment 6; Sheet A027-1BC; Occupancy Groups: Please indicate the correct Occupancy Group per the IBC Chapter 3. 2. Previous Comment 8; Sheet A027-1BC; Exiting Calculation: Please indicate the total exit width required, and the total exit width provided. 3. Previous Comment 14; Sheets A301-1BC and A301-1BD; Key Notes: Notes 1, 2, and 3 were not located. Please verify. 4. General: Please provide written responses to all review comments. |
| 09/17/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | As per the previous electrical plan review, it was requested to assign a branch circuit and panel for the lighting and provide correlation with the panel schedule. The room numbers shown in the panel schedules still do not correlate with actual room numbers shown on the architectural plans. For clarification, please show the room numbers on the electrical floor plans. Ref; 2012 IBC 107.2.1, 2011 NEC art 408.4 |