Permit Number: T18CM06033
Parcel: 140260360

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM06033
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/14/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A027-B; Specify the correct Assembly occupancy type in the USE TABLE as A-3 occupancy per IBC 311.2

2. Sheet A027-1B: Indicate the required amount of the total exit width based on the total occupant load multiplied by the correct exit width factor of 0.15 per IBC Section 1005.3.2 (Exception) and indicate the total exit width provided.

3. Sheet A201-1B Specify out of sequence Notes as NOT USED if not contained in the notes sections of the plans. IBC 107.2.1

4. Notes that have been deleted from the NOTES section must be labeled as NOT USED. IBC 107.2.1

5. General: Please provide written responses to all review comments.
09/14/2018 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Approved