Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM06033
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/14/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A027-B; Specify the correct Assembly occupancy type in the USE TABLE as A-3 occupancy per IBC 311.2 2. Sheet A027-1B: Indicate the required amount of the total exit width based on the total occupant load multiplied by the correct exit width factor of 0.15 per IBC Section 1005.3.2 (Exception) and indicate the total exit width provided. 3. Sheet A201-1B Specify out of sequence Notes as NOT USED if not contained in the notes sections of the plans. IBC 107.2.1 4. Notes that have been deleted from the NOTES section must be labeled as NOT USED. IBC 107.2.1 5. General: Please provide written responses to all review comments. |
| 09/14/2018 | GPERU1 | ELECTRICAL-COMMERCIAL | REVIEW | Approved |