Permit Number: T18CM06022
Parcel: 10409015E

Address:
855 W WETMORE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM06022
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2018 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change Reviewer: Chris Anderson, October 9, 2018
BUILDING – COMMERCIAL
In response to previous building review comment 4, the deletion of detail 2A/A145 is noted; however the location(s) for detail 2B/A145 is still not identified on the reflected ceiling plan. Ref. 2012 IBC 107.2.1.
In response to previous building comment 6, the submitted PAREX details do not correspond to EIFS sill details 5, 16 and 18/A523. PAREX details show EIFS terminating minimum 2” above pavement. In all cases, the PAREX vented bottom track is located 1” below the foundation plate line to eliminate the possibility of water entering the building behind the track. The referenced details on sheet A523 do not appear to comply with PAREX installation standards. Ref. 2012 IBC 1408.5.
10/11/2018 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change Reviewer: Chris Anderson, October 9, 2018
MECHANICAL – COMMERCIAL
Regarding previous Mechanical review comment 2, no mechanical COMcheck was included in the resubmittal. Ref. 2012 IMC 106.3.1.
10/11/2018 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change Reviewer: Chris Anderson, October 9, 2018
ELECTRICAL – COMMERCIAL
Per the 2012 City of Tucson/Pima County Outdoor Lighting Code 402.1 the color temperature rating of exterior light fixtures shall not exceed 3,500 K. Please reselect the E1f light fixture for the exterior canopy shown in the Lighting Fixture Schedule, sheet E002. Regarding response to previous electrical comment 1, while new light fixture L1g was added to the light fixture schedule, the canopy lights on lighting plan, sheet E201, were not changed to L1g.
10/11/2018 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Completed