Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T18CM05996
Parcel: 135074920

Address:
7666 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM05996
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2018 NROSS1 ZONING REVIEW Approved
08/03/2018 GPERU1 MECHANICAL-COMMERCIAL REVIEW Completed
08/03/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
08/03/2018 NROSS1 ENGINEERING REVIEW Passed
08/03/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/03/2018 GPERU1 WATER REVIEW Passed
08/03/2018 GPERU1 PLUMBING-COMMERCIAL REVIEW Completed
08/03/2018 JVINCEN1 FIRE REVIEW Approved
08/03/2018 GPERU1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed