Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM05995
Parcel: 114540640

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM05995
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed; only 1040 CFM of exhaust has been provided. [Initial comment: The amount of outside air supplied to a space shall be approximately equal to the amount of air exhausted from the space. A nail salon requires a minimum exhaust flow rate of 0.6 CFM per square foot of net occupiable space. The minimum amount of outside air to be supplied to the space is based on 25 people per square foot, 20 CFM per person, and 0.12 CFM per square foot. At 1720 square feet, this would be 1066 CFM of supply and 1032 CFM of exhaust. Reference: Section 403.3, IMC 2012.
2. Comment not addressed. [Initial comment: Revise the size and material of the proposed clothes dryer duct per Section 504.6.1, IMC 2012.
3. Revise the specified termination of the clothes dryer vent per Section 504.4, IMC 2012 and per the manufacturer's instructions. Reference: Section 504.6.2, IMC 2012.
09/10/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Comment not addressed. [Initial comment: Provide water isometrics and waste & vent isometrics for the new plumbing work. Clarify how the horizontal branch serving the two new lavatories is to "tap" to the existing mop sink "waste riser". Reference: Section 107.2.1, IBC 2012.]
2. Comment not addressed. [Initial comment: Verify that the fixture drain for the automatic clothes washer complies with the requirements of Section 406.2, IPC 2012.]
3. Comment not addressed. [Initial comment: Provide a detail showing how a flow-reduction valve (Section 424.7, IPC 2012) called out in item #7 of the plumbing plan notes will be employed. Reference: Section 107.2.1, IBC 2012.]
4. Comment not addressed. [Initial comment: The developed length of the hot water supply piping appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2012.]
5. Comment not addressed. [Initial comment: A check valve is not listed as a backflow preventer. Provide a backflow preventer listed for the application. Reference: Section 608.1, IPC 2012.]
6. Comment not addressed. [Initial comment: Provide indirect waste receptors with traps to serve the pedicure chairs. Reference: Section 1002.1, IPC 2012.]
7. Comment not addressed. [Initial comment: Clarify the method used to vent the drains for the pedicure chairs. Reference: Sections 902.1 and 918.7, IPC 2012.]
8. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for business occupancy (e.g. drinking fountains). See demolition keynote #20 on sheet A-01.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/18/2018 QJONES1 APPROVAL SHELF Completed
09/18/2018 QJONES1 OUT TO CUSTOMER Completed
09/18/2018 QJONES1 REJECT SHELF Completed