Permit Number: T18CM05939
Parcel: 128100810

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM05939
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/10/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The depiction of the lavatory on the partial waste & vent isometric, B/P2.0, appears to show the fixture drain for the lavatory as being both individually-vented (Section 910.1, IPC 2012) and common-vented with the water closet (Section 911.1, IPC 2012): which is it to be? Reference: Section 107.2.1, IBC 2012.
08/10/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed