Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/10/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The depiction of the lavatory on the partial waste & vent isometric, B/P2.0, appears to show the fixture drain for the lavatory as being both individually-vented (Section 910.1, IPC 2012) and common-vented with the water closet (Section 911.1, IPC 2012): which is it to be? Reference: Section 107.2.1, IBC 2012.
08/10/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed