Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM05939
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/02/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/10/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The depiction of the lavatory on the partial waste & vent isometric, B/P2.0, appears to show the fixture drain for the lavatory as being both individually-vented (Section 910.1, IPC 2012) and common-vented with the water closet (Section 911.1, IPC 2012): which is it to be? Reference: Section 107.2.1, IBC 2012. |
08/10/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed |