Permit Number: T18CM05913
Parcel: 122120630

Review Status: Active

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM05913
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Anchor Test Report; Sheet S.000: The Test Report indicates that APA Solar Racking recommends the helical piles setup to be 3.5" helix at 28" embedment. Sheet S.000 indicates anchor/foundation testing report is site specific and only where required by EOR or AHJ. With the Anchor Test Report indicating the helix criteria for this site, no indication of these anchors was found on the drawings. Are these anchors required for this permit? Please indicate this information on Sheet S.000, and provide the location and anchor specifications on another S-series drawing.
2. Structural Calculations: The structural analysis for the bent anchor post (1.9 x 0.120) was not located in the calculations. Please verify.
3. General: Please provide written responses to all review comments.
08/29/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide for an NRTL field evaluation, or show in detail the method and materials used to provide a listed supply side PV interconnection that is verified through the equipment manufacturer as to not compromise the performance and listing of the equipment. NEC 110.3.
#2. Provide more detail on the one or three line diagram showing the PV source conductor arrangement for each of the 18 module circuits including the use of listed combiners or j-boxes.
Ref; 2012 IBC 107.2.1, 2011 NEC

Final Status

Task End Date Reviewer's Name Type of Review Description
08/01/2018 ANY REJECT SHELF RECEIVED