Permit Number: T18CM05904
Parcel: 11504334A

Address:
328 E HELEN ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM05904
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2018 AVAUGHN1 ZONING REVIEW Needs Review
09/25/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide the revised M1.0 sheet.
09/25/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Plan Sheets; E1.0, E0.2. As per the previous electrical plan review comment #2 (exterior lighting). Please identify the exterior lighting with a mark or symbol that correlates with the lumen calcs for clarification.
#2. Provide a note stating a special inspection required. Sec 106.2.1
2012 IBC 107.2.1, Tucson/Pima County Outdoor Lighting Code.
09/25/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 28; Sheet S1.0; Design Loads: It does not appear the calculations or the drawings indicate a higher live load at the attic. Please verify.
09/25/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change An individual vent is limited to serving only two fixtures (i.e. common venting). Reference: Section 911.1, IPC 2012. [Initial comment: Revise the piping layout shown in detail D/P1.0 for P-1, P-1A and P-2B and similarly P-1A and P-2A in detail A/P1.0. A plumbing vent may not be used for any purpose other than venting of the plumbing system (e.g. the horizontal drain for P-1A is connecting to the vent for P-2B). Reference: Section 901.4, IPC 2012.]

Final Status

Task End Date Reviewer's Name Type of Review Description
09/25/2018 AVAUGHN1 REJECT SHELF Completed