Permit Number: T18CM05897
Parcel: 11618434A

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T18CM05897
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/16/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/18/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
10/18/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
10/25/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
As per the previous plan review comments and responses, the following comments were generated from the responses.
#1. Comment and response to #1 (a) . Still need compliance with the 2012 IECC. Read the entire exception… Also See section R201, R404.1
Ref; 2012 IBC 107.2.1, 2011 NEC,
11/01/2018 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Site Section Manager

PROJECT: 427 N. Grande Ave #1
T18CM05888, T18CM05896 & T18CM05897
Building Plan (1st Review)

TRANSMITTAL DATE: November 1, 2018

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The building plans have been reviewed for compliance with development package DP18-0084 and appear to meet all requirements.

3. Until all other PDSD review agencies have approved the building plans zoning cannot approve.

4. The Civil sheets C1, C2, C3, C4, C5, C6 and Landscape sheets L1.1, L2.1 & L2.2 are not part of DP18-0084 as indicated on the plan and have not been reviewed or approved. A new grading/landscape submittal review will be required and must be approved.


If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956