Permit Number: T18CM05888
Parcel: 11618434A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM05888
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/05/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/05/2018 DAVID RIVERA ZONING REVIEW Approved
12/17/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
12/17/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
12/18/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; Plan Sheet E1.1. Tucson/Pima County Outdoor Lighting Code.
In this submittal a note (DELTA 2) was added stating that the exterior building lighting was being upgraded to LED luminaires and the plans show all the buildings included, however the three permit activities are for buildings 1, 2, and 3. Please revise the plans to exclude the lighting upgrades for the other buildings, or revise the permits to include the other buildings.
2012 IBC sec 107.2.1, Outdoor Lighting Code. City of Tucson Commercial Plan Submittal Requirements.
12/28/2018 JOHN VAN WINKLE ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/03/2019 QJONES1 APPROVAL SHELF Completed
01/03/2019 QJONES1 OUT TO CUSTOMER Completed