Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM05888
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/05/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/05/2018 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 12/17/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 12/17/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 12/18/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref; Plan Sheet E1.1. Tucson/Pima County Outdoor Lighting Code. In this submittal a note (DELTA 2) was added stating that the exterior building lighting was being upgraded to LED luminaires and the plans show all the buildings included, however the three permit activities are for buildings 1, 2, and 3. Please revise the plans to exclude the lighting upgrades for the other buildings, or revise the permits to include the other buildings. 2012 IBC sec 107.2.1, Outdoor Lighting Code. City of Tucson Commercial Plan Submittal Requirements. |
| 12/28/2018 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/03/2019 | QJONES1 | APPROVAL SHELF | Completed |
| 01/03/2019 | QJONES1 | OUT TO CUSTOMER | Completed |
| 01/03/2019 | QJONES1 | REJECT SHELF | Completed |