Permit Number - T18CM05866
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
Ref; Lumen Calcs.
(a) Incorrect allowable lumen amount. Area 3- Option 3 is used for both Full Cut-Off and Unshielded. 175000 (Full Cut-Off) - 11000 (Unshielded)=164000 x .71 (acres)= 116440 Allowed vs 146624 Proposed. The Proposed lumen amount exceeds the allowable for this parcel.
(b) Because all the lighting proposed is Full Cut-Off, Option 2 would be the better choice.
250000 x .71 (acres)= 177500 Allowed FCO lumens vs 146624 Proposed.
The proposed lumen amount is within the allowable.
(c) The Full Cut-Off under canopy luminaires are exempt from the lumen inventory but are still included in the proposed lumens.
(d) For future projects, please include the lumen calcs on the site plan or lighting plan sheet.
Ref; Tucson/Pima County Outdoor Lighting Code.