Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM05866
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/29/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/29/2018 | GPERU1 | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Compliance with the 2012 City of Tucson/Pima County Outdoor Lighting Code requires documentation on the plans to demonstrate compliance with the lumen cap per Table 401.1, and which requires the following information: 1. Each exterior luminair type with the lumens for that type, the quantity or each type and whether the luminaire is full cut-off or unshielded. 2. The total of full cut-off and unshielded lumens for the parcel. 3. A statement of the lighting area, the size of the permitted parcel, and the maximum allowable full cut-off or unshielded lumens. 4. Note on plans indicating whether a special inspection is required in accordance with Section 106. |