Permit Number: T18CM05866
Parcel: 117091490

Address:
145 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM05866
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2018 KELLY LEE ZONING REVIEW Approved
07/30/2018 KLEE1 ENGINEERING REVIEW Passed
07/30/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
Provide full compliance with the Tucson/Pima County Outdoor Lighting Code. This Code can be printed or downloaded from www.tucsonaz.gov/pdsd. See section 104 for plan submittal requirements.
07/30/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Please submit structural calculations for the light pole foundation base.
07/30/2018 GPERU1 MECHANICAL-COMMERCIAL REVIEW Passed