Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T18CM05731
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Active
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/24/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
07/25/2018 | NROSS1 | ZONING | REVIEW | Approved | |
07/25/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. The stage is required to be accessible; provide ADA ramp or platform lift. 2. Specify if space under stage is to be used for storage. 3. Coordinate the beams specified on the structural calcs. with the floor framing plan. The struct. calcs. list 4 separate types of beams. 4. Provide a detail of the posts connection to new footing. Specify post base and post size, type of material. |
07/27/2018 | AVAUGHN1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
07/27/2018 | AVAUGHN1 | ENGINEERING | REVIEW | Needs Review |