Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T18CM05728
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2018 NROSS1 ZONING REVIEW Approved
09/28/2018 NROSS1 ENGINEERING REVIEW Passed
09/28/2018 NROSS1 NPPO REVIEW Passed
10/05/2018 TWEIDEM1 BUILDING-RESIDENTIAL REVIEW Completed 1. Please enlarge construction details; per City of Tucson ordinance, font sizes cannot be less than 3/32 inche in size.
2. Indicate on the plan where WALL SECTION detail occurs on the plans.
3. Provide loading and calculations for sizing header for support of main ridge beam; include with plans.
4. Provide the size of the mechanical HVAC on the plans.
5. Indicate exterior outlets are WP-GFCI protected.
6. Specify that all new interior outlets are AFCI protected.
7. Indicate the roof covering material on the roof.
8. The electrical plan indicates a 60 amp subpanel; show where panel will be located and specify the feeders to the subpanel.
8. Specify the size of the beam for the patio.