Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM05701
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/31/2018 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 08/06/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | 1. A2.0 Provide references to the call outs on details shown on this sheet. IBC 107.2.1. 2. The plumbing calculation for the A-3 occupancy on level 2 is short by (1) watercloset for male and female use. The minimum required number of waterclosets for male and female is 6 each. An accessible family or assisted use toilet room shall be provided where the aggregate of 6 or more male and female water closets is required. IBC 1109.2.1. 3. Provide structural drawings-details of the work described in the structural calculations and show where such work occurs. IBC 107.1. 4. A-2.0 Show where the detailsl for the large openeing in the floor are located and coordinate with the structural calculations. IBC 107.2.1. 5. A-3.1 Provided details and attacments for all new walls and partitions to the floor and roof ceiling. New walls must be capable of withstanding not less than 5 pounds per square foot horizontal load. 6. A2.3 Where new partitions or walls are being installed in toilet rooms, provide an enlarged toilet floor plan and show all dimensions for accessibility and maneuvering clearanges. Show stall demensions. ICC A117.1. 7. Provide an enlarged floor plan of accessible family-assisted use toilets. Show all required maneuvering clearance dimensions. The water closet is required to have a clearance of not less than 5 ft. in width. Show on the floor plan. ICC A117.1. |
| 08/10/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/10/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Waste & vent isometric 4/P-2.1 calls out a ½" traparm for fixture P-1. Reference: Section 709.2, IPC 2012. 2. Clarify detail 3/P-2.1; are you intending to use a common vent for P-1 and P-2 or are you using the vent of P-1 as a drain? See Section 911, IPC 2012. 3. The "below deck mechanical mixing valve (BDM)" specified for the lavatory supplies does not provide automatic control of the water temperature. Specify a mixing valve listed to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012. |
| 08/10/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 08/21/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |