Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T18CM05558
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/24/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Revise the lumen calcs for outdoor lighting. (a) Area 'E3- option 2' allows for 250,000 lumens per acre, not 300,000. (b) A special inspection will be required per section per 106.2.1. (c) Provide evidence that the under canopy luminaires are full cut-off, and the light source color temperature for all exterior lighting does not exceed 3500K. Section 402.1, 402.2(3) Ref; Tucson/Pima County Outdoor Lighting Code. |
| 09/21/2018 | MMORENO1 | ENGINEERING | REVIEW | Passed | |
| 09/21/2018 | MMORENO1 | ZONING | REVIEW | Approved | |
| 09/21/2018 | AVAUGHN1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 09/21/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/21/2018 | AVAUGHN1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 09/21/2018 | AVAUGHN1 | FIRE | REVIEW | Completed | |
| 09/21/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/21/2018 | AVAUGHN1 | APPROVAL SHELF | Completed |
| 09/21/2018 | AVAUGHN1 | OUT TO CUSTOMER | Completed |
| 09/21/2018 | AVAUGHN1 | REJECT SHELF | Completed |