Permit Number: T18CM05557
Parcel: 12310001C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM05557
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2018 MARTIN BROWN FIRE REVIEW Approved
08/01/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/01/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet G101; Life Safety Plan: The Storage Room to the west of the Formula Preparation Room indicates one hour fire resistant rated fire barriers for the east, south, and west walls. Please indicate in the Code Analysis the section of the IBC that requires that rating.
2. Sheet G101; Occupancy Analysis Table: The maximum allowable exit access travel distance for Rooms 4-100,
4-100A, and 4-100B indicates 300 feet in this table, while the IBC Table 1016.2 indicates 200 feet for an I-2 occupancy classification. Please verify. These rooms are listed as a "B" occupancy classification, but must be analyzed for the I-2 hospital occupancy classification. Please verify.
3. Sheet A601; Door Schedule: Please indicate in the Door General Notes to reference the project specifications for the door hardware (Section 087100).
4. General: Please provide written responses to all review comments.
08/02/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Fire dampers are shown in the main supply and return ducts to the terminal unit. How are the fire dampers mounted?
2. Provide fire dampers for the supply and return ducts serving the storage room.
08/02/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
08/02/2018 ROBERT SHERRY WATER REVIEW Completed
08/09/2018 DAVID RIVERA ZONING REVIEW Approved
08/14/2018 JOHN VAN WINKLE ENGINEERING REVIEW Passed
08/17/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/17/2018 TWEIDEM1 APPROVAL SHELF Completed
08/17/2018 TWEIDEM1 OUT TO CUSTOMER Completed
08/17/2018 TWEIDEM1 REJECT SHELF Completed