Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM05557
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/24/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 08/01/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/01/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet G101; Life Safety Plan: The Storage Room to the west of the Formula Preparation Room indicates one hour fire resistant rated fire barriers for the east, south, and west walls. Please indicate in the Code Analysis the section of the IBC that requires that rating. 2. Sheet G101; Occupancy Analysis Table: The maximum allowable exit access travel distance for Rooms 4-100, 4-100A, and 4-100B indicates 300 feet in this table, while the IBC Table 1016.2 indicates 200 feet for an I-2 occupancy classification. Please verify. These rooms are listed as a "B" occupancy classification, but must be analyzed for the I-2 hospital occupancy classification. Please verify. 3. Sheet A601; Door Schedule: Please indicate in the Door General Notes to reference the project specifications for the door hardware (Section 087100). 4. General: Please provide written responses to all review comments. |
| 08/02/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Fire dampers are shown in the main supply and return ducts to the terminal unit. How are the fire dampers mounted? 2. Provide fire dampers for the supply and return ducts serving the storage room. |
| 08/02/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 08/02/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 08/09/2018 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 08/14/2018 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed | |
| 08/17/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/17/2018 | TWEIDEM1 | APPROVAL SHELF | Completed |
| 08/17/2018 | TWEIDEM1 | OUT TO CUSTOMER | Completed |
| 08/17/2018 | TWEIDEM1 | REJECT SHELF | Completed |