Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T18CM05552
Parcel: 140420740

Address:
7250 S TUCSON BL

Review Status: Active

Review Details: RESUBMITTAL

Permit Number - T18CM05552
Review Name: RESUBMITTAL
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2018 MARTIN BROWN FIRE REVIEW Approved
08/24/2018 ROBERT SHERRY WATER REVIEW Completed