Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T18CM05551
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/06/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/13/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/27/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. At this plan review, it was realized that the service equipment is Ground Fault Protected at the main service disconnect. This would require that the PV interconnection to be on the supply side of the Ground Fault equipment at the service, or a supply side interconnection, Per NEC 705.12D(3). Or per the exception to this article, the AC feeders from the inverters or the backfed OCPD device, would have to have Ground Fault Protection. All Ground Fault Protective devices shall be rated for backfeeding. Ref; 2011 NEC 690.64 and 705.12 D(3). |
| 11/28/2018 | TOM WEIDEMAN | ZONING | REVIEW | Passed | |
| 11/28/2018 | TOM WEIDEMAN | ENGINEERING | REVIEW | Passed |