11/06/2018 MARTIN BROWN FIRE REVIEW Approved
11/13/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/27/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. At this plan review, it was realized that the service equipment is Ground Fault Protected at the main service disconnect. This would require that the PV interconnection to be on the supply side of the Ground Fault equipment at the service, or a supply side interconnection, Per NEC 705.12D(3). Or per the exception to this article, the AC feeders from the inverters or the backfed OCPD device, would have to have Ground Fault Protection. All Ground Fault Protective devices shall be rated for backfeeding.
Ref; 2011 NEC 690.64 and 705.12 D(3).