Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T18CM05546
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/27/2018 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Section Manager PROJECT: 8000 S. Rita Road T18CM05546 Building Plan (1st Revision) TRANSMITTAL DATE: December 27, 2018 1. The building plans, odor mitigation plan have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Exhibit 1, Odor Mitigation Site Plan does not match the approved development package (DP). The exhibit labels PAD 2 as a building and also as "OUTDOOR GROW AREA" If you are proposing to have additional outdoor grow areas other than what is shown on the approved DP than a revision is required to the DP. 3. It is not clear where the proposed fans and vapor system will receive the electrical power from. Electrical sheets within the building set may need to be modified. 4. Plans for the odor mitigation will need to be added to the building plan set. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |