Permit Number: T18CM05546
Parcel: 14111024C

Address:
8000 S RITA RD

Review Status: Completed

Review Details: 3RD PARTY REVIEW - COMMERCIAL

Permit Number - T18CM05546
Review Name: 3RD PARTY REVIEW - COMMERCIAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/25/2018 MARTIN BROWN FIRE REVIEW Reqs Change Please provide a Hazardous Material Inventory Statement, with listings, quantities, and open or closed uses.
Indicate method of storing hazardous materials.
Please provide information regarding extraction process.
08/08/2018 ROBERT SHERRY WATER REVIEW Reqs Change Tucson Water limits a 1" meter to a maximum demand of 37.5 GPM. Provide a letter from Tucson Water confirming that the use of a 1" water meter will be allowed for this project.
08/08/2018 EHAMBLI1 ZONING REVIEW Reqs Change FROM: Elisa Hamblin, AICP
Lead Planner
PDSD Zoning Review Section

PROJECT: T18CM05546
Building Plans (1st Review), New Metal Building
8000 S. Rita Rd, R-1 Zoning

TRANSMITTAL DATE: August 8, 2018

DUE DATE: August 13, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the building plans but cannot approve them at this time. An approved development package (DP) is needed for comparison at the time of the building plan review by zoning.

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP. (Include a copy of the revised and approved DP (with PDSD stamp) with the next building submittal.) The PDSD approved and signed copy of the DP shall not be incorporated into the building plans unless it is a PDSD approved and stamped copy.

3. COMMENT: If any changes are necessary, due to the PDSD Commercial Plan Reviewer's comments that affect or change the building footprint, height, or square footage, the DP will need to be updated prior to approval of the building plans by Zoning.

4. COMMENT: Once the plans have been reviewed and approved by the Commercial Plan Reviewers and zoning has verified consistency with the PDSD approved and signed copy of the DP, the building plans can be approved by zoning.

5. COMMENT: The revised DP could be potentially handled as an over-the-counter walk through. Please contact me if you wish to proceed in this manner.

If you have any questions please contact me at Elisa.Hamblin@tucsonaz.gov or (520) 837-4966.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Building plans and revised and approved version of the DP as reference.
09/20/2018 STANTEC 3RD PARTY REVIEW-COMMERCIAL AT 3RD PARTY OFFICE Completed
09/20/2018 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/20/2018 KROBLES1 OUT TO CUSTOMER Completed