Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment. Also provide a written response.
1. Provide a schematic or wiring diagram showing the wiring method for the operation of the Emergency Power Off Button.
2. Indicate the branch circuit utilized for the new EF and show this on the panel schedule.
Ref; 2012 IBC sec 107.2.1, 2011 NEC 408.4
01/10/2019 MASHFOR1 FIRE REVIEW Approved
01/10/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed