Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T18CM05524
Review Name: WALK THRU - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/10/2019 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comment. Also provide a written response. 1. Provide a schematic or wiring diagram showing the wiring method for the operation of the Emergency Power Off Button. 2. Indicate the branch circuit utilized for the new EF and show this on the panel schedule. Ref; 2012 IBC sec 107.2.1, 2011 NEC 408.4 |
| 01/10/2019 | MASHFOR1 | FIRE | REVIEW | Approved | |
| 01/10/2019 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed |