Permit Number: T18CM05522
Parcel: 133152920

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T18CM05522
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2018 MARTIN BROWN FIRE REVIEW Approved
08/03/2018 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. Show the branch circuit wiring method to the new site light; indicate circuit identification. If using tap method, show location of tap. Show light and branch circuit on electrical site plan.
2. Provide compliance with the Tucson/Pima County Outdoor Lighting Code. If claiming exemption per section 401.2.1(3), verify full cut-off shielding.
08/03/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/14/2018 KROBLES1 OUT TO CUSTOMER Completed