Permit Number: T18CM05520
Parcel: 11706168C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM05520
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2018 STEVE SHIELDS ZONING REVIEW Approved
07/16/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/16/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Is the disconnect switch for panel 'A' new or existing. Please indicate AMP, VOLTAGE, FUSE TYPES and SIZES.
#2. The branch circuit shown for EF 1 and 2 does not correlate with the panel schedule.
REF; 2012 IBC sec 107.2.1, 2011 NEC.
07/16/2018 SSHIELD1 ENGINEERING REVIEW Passed
07/16/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Coordinate the design of the water heater support with the architect.
07/16/2018 ROBERT SHERRY WATER REVIEW Completed
07/20/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Approved 1. Provide structural calculations for the water heater stand supported from framed wall.
2. Page 10 of the structural calculations show a 5.125 x 16.5 GLB; show where located on the structural calculations or remove page. Verify.
07/20/2018 JVINCEN1 FIRE REVIEW Approved
07/20/2018 AVAUGHN1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved APOVED BY GPERU1
07/20/2018 SSHIELD1 DESIGN PROFESSIONAL REVIEW Passed Interior work only. Design Prof not needed.