Permit Number: T18CM05518
Parcel: 11712098A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM05518
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2018 EHAMBLI1 ZONING REVIEW Approved
07/16/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/16/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/16/2018 EHAMBLI1 ENGINEERING REVIEW Passed
07/16/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Approved
07/16/2018 ROBERT SHERRY WATER REVIEW Completed
07/16/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The cofee maker requirs the use of a dual check backflow preventer listed to ASSE 1022. Provide relief piping to an indirect reciever where it will not cause damage. Reference: Sections 608.14.2.1 and 608.16.10, IPC 2012.
2. Show the supply and drain connections of the dishwasher.
07/16/2018 MARTIN BROWN FIRE REVIEW Approved
07/16/2018 GPERU1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed