Permit Number: T18CM05494
Parcel: 13416205D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM05494
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2018 KELLY LEE ZONING REVIEW Approved
07/24/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Clarify the duct configuration for the energy recovery unit.
07/24/2018 KLEE1 ENGINEERING REVIEW Passed
07/24/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/24/2018 MARTIN BROWN FIRE REVIEW Approved
07/24/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Verify the water distribution piping is adequately sized.
07/24/2018 ROBERT SHERRY WATER REVIEW Reqs Change The water demand calculations show that the existing water meter would have to deliver 39.2 GPM. The maximum demand for a 1" meter is 37.5 GPM. Contact Tucson Water to resolve this situation.
07/24/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/24/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/07/2018 QJONES1 APPROVAL SHELF Completed
08/07/2018 QJONES1 OUT TO CUSTOMER Completed
08/07/2018 QJONES1 REJECT SHELF Completed