Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM05494
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/24/2018 | KELLY LEE | ZONING | REVIEW | Approved | |
| 07/24/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Clarify the duct configuration for the energy recovery unit. |
| 07/24/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/24/2018 | KLEE1 | ENGINEERING | REVIEW | Passed | |
| 07/24/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/24/2018 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | The water demand calculations show that the existing water meter would have to deliver 39.2 GPM. The maximum demand for a 1" meter is 37.5 GPM. Contact Tucson Water to resolve this situation. |
| 07/24/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify the water distribution piping is adequately sized. |
| 07/24/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/24/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/07/2018 | QJONES1 | APPROVAL SHELF | Completed |
| 08/07/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
| 08/07/2018 | QJONES1 | REJECT SHELF | Completed |