Permit Number: T18CM05449
Parcel: 13316024L

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM05449
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2018 EHAMBLI1 ZONING REVIEW Approved
07/16/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/16/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/16/2018 EHAMBLI1 ENGINEERING REVIEW Passed
07/16/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Key note no. 3 is not on the demolition plan. Please indicate note reference on the demo plan. D1
2. Specify how the partition/demizing walls are constructed that will have door openings installed. D1
3. Indicate where nearest restrooms are located for use by the tenants in the office expansion; indicate travel distance to restrooms and whether they are public facilities.
4. Privide a life-safety exiting plan and note the exit door locations, common path of egress travel and travel distance.
5. Drinking fountain required that can be used by standing persons and persons in wheelchairs. Alternate is a water dispensing unit that is piped to the water distribution and in an accessible location.
6. Label and show the location of all exit doors.
07/16/2018 ROBERT SHERRY WATER REVIEW Completed
07/16/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/16/2018 MARTIN BROWN FIRE REVIEW Approved
07/16/2018 GPERU1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
07/17/2018 QJONES1 APPROVAL SHELF Completed
07/17/2018 QJONES1 OUT TO CUSTOMER Completed
07/17/2018 QJONES1 REJECT SHELF Completed