Permit Number: T18CM05355
Parcel: 132165940

Address:
1840 E BENSON HY

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM05355
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2018 GPERU1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
07/11/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/11/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/11/2018 SSHIELD1 ENGINEERING REVIEW Passed
07/11/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Provide the occupant load for the new classroom
2. The patio/classroom appears to be located at a main exit access location. The exit is not allowed to pass through a room or area that can be locked to prevent egress.
3. Specify door tags on the floor plan that reference the DOOR SCHEDULE.
4. Specify the location of the MAG LOCK entry doors and provide a door sequence of operation for deactivation upon loss of power or fire alarm activation.
5. Specify the occupant load of the new classroom.
6. Provide a life-safety egress exiting plan that includes the egress travel and number of occupants at each exit.
7. Structural calculations are required for the new footing/stemwall and headers over openings. Provide lateral calculations with struct. calcs.
8. Specify the ceiling height of the classroom.
9. Label the classroom on the floor plan.
10. Provide the size of the classroom.
07/11/2018 ROBERT SHERRY WATER REVIEW Completed
07/11/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
07/11/2018 MARTIN BROWN FIRE REVIEW Approved
07/18/2018 QJONES1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/18/2018 QJONES1 APPROVAL SHELF Completed
07/18/2018 QJONES1 OUT TO CUSTOMER Completed
07/18/2018 QJONES1 REJECT SHELF Completed