Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM05329
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/24/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Verify the ac unit circuit load requirements. It appears some units have heat strips. Revise OCPD rating circuit conductor sizing. Reflect any modifications necessary to electrical on the plans. Ref; 2012 IBC 107.2.1, 2011 NEC. |
| 07/24/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 07/24/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 07/24/2018 | ROBERT SHERRY | WATER | REVIEW | Completed |