Permit Number: T18CM05317
Parcel: 14026002F

Address:
2200 E DREXEL RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM05317
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2018 MARTIN BROWN FIRE REVIEW Approved
07/20/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment. Also provide a written response.
#1. Ref; Plan Sheet PV 3.0. PV 4.0.
(a) The one diagram has the lettering GFP shown by the existing electrical service main disconnect. Does this mean the equipment is Ground Fault Protected? If yes, then please address NEC art 705.12(d)(3). Please clarify.
#2. Please provide more detail (Wiring Methods) utilized to extend the existing lighting branch circuit to the new canopy luminaires.
Ref; 2012 IBC sec 107.2.1, 2011 NEC.
07/26/2018 DAVID RIVERA ZONING REVIEW Passed
07/31/2018 JOHN VAN WINKLE ENGINEERING REVIEW Passed
08/03/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved