Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T18CM05317
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/19/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/20/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comment. Also provide a written response. #1. Ref; Plan Sheet PV 3.0. PV 4.0. (a) The one diagram has the lettering GFP shown by the existing electrical service main disconnect. Does this mean the equipment is Ground Fault Protected? If yes, then please address NEC art 705.12(d)(3). Please clarify. #2. Please provide more detail (Wiring Methods) utilized to extend the existing lighting branch circuit to the new canopy luminaires. Ref; 2012 IBC sec 107.2.1, 2011 NEC. |
| 07/26/2018 | DAVID RIVERA | ZONING | REVIEW | Passed | |
| 07/31/2018 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Passed | |
| 08/03/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/06/2018 | TWEIDEM1 | APPROVAL SHELF | Completed |
| 08/06/2018 | TWEIDEM1 | OUT TO CUSTOMER | Completed |
| 08/06/2018 | TWEIDEM1 | REJECT SHELF | Completed |