Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM05300
Parcel: 12407113A

Address:
951 E 10TH ST #2

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM05300
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/24/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Verify the ac unit circuit load requirements. It appears some units have heat strips. Revise OCPD rating circuit conductor sizing. Reflect any modifications necessary to electrical on the plans.
Ref; 2012 IBC 107.2.1, 2011 NEC.
07/24/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/24/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
07/24/2018 ROBERT SHERRY WATER REVIEW Completed