Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM05222
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/05/2018 | MMORENO1 | ZONING | REVIEW | Approved | |
| 07/05/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 07/05/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/05/2018 | MMORENO1 | ENGINEERING | REVIEW | Passed | |
| 07/05/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Per IBC 2902.2 separate restroom facilities are required for each sex when the occupant load is over 15 in a A-2 occupancy. 2. Family assist, or unisex restrooms are allowed where facilities are required for each sex and each toilet facility is required to have only 1 water closet. 3. Provide attachment details for new walls at the roof/ceiling. |
| 07/05/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 07/05/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for assembly occupancy. |
| 07/05/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/05/2018 | GPERU1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |