Permit Number: T18CM05222
Parcel: 11207168A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM05222
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/05/2018 MMORENO1 ZONING REVIEW Approved
07/05/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
07/05/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/05/2018 MMORENO1 ENGINEERING REVIEW Passed
07/05/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Per IBC 2902.2 separate restroom facilities are required for each sex when the occupant load is over 15 in a A-2 occupancy.
2. Family assist, or unisex restrooms are allowed where facilities are required for each sex and each toilet facility is required to have only 1 water closet.
3. Provide attachment details for new walls at the roof/ceiling.
07/05/2018 ROBERT SHERRY WATER REVIEW Completed
07/05/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for assembly occupancy.
07/05/2018 MARTIN BROWN FIRE REVIEW Approved
07/05/2018 GPERU1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
07/10/2018 QJONES1 APPROVAL SHELF Completed
07/10/2018 QJONES1 OUT TO CUSTOMER Completed
07/10/2018 QJONES1 REJECT SHELF Completed