Review Date Reviewer's Name Type of Review Description Status Comments
07/19/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/19/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide a detail showing how the hood is connected to the roof structure. [Initial comment: Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2012.]
07/19/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed