Permit Number: T18CM05211
Parcel: 115211520

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM05211
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/05/2018 MMORENO1 ZONING REVIEW Approved
07/05/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify the wall covering along the side of the hood. Show that the hood installation complies with Section 507.9, IMC 2012 with regard to a smooth, cleanable, non-absorbent, and non-combustible material installed between the hood and the wall, and extending 18" beyond the hood.
2. Provide structural calculations and details to show that the Type I hood is supported from the building structure in accordance with Section 507.6, IMC 2012 (the hood hanging weight plus the weight of personnel working in or on the hood). Reference: Section 302.1, IMC 2012.
3. Show that the roof top air-conditioning units supplying make up air for the kitchen hood are electrically interlocked to the exhaust fans. Reference: Section 508.1, IMC 2012.
07/05/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
07/05/2018 MMORENO1 ENGINEERING REVIEW Passed
07/05/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. Access to a required public restroom cannot be through a kitchen area.
2. Per IBC 2902.2 separate restroom facilities are required for A-2 occupancy with an occupant load over 15.
3. Structural calculations and details are required for the support of the dead and live load of required kitchen hoods.
4. Provide structural calculations and details for the water heater platform if not supported by floor.
5. Provide an egress plan and show the common path of egress travel and travel distance.
6. Submit enlarged ADA restroom elevations that show grab bars, dispensers, and plumbing fixture heights.
07/05/2018 ROBERT SHERRY WATER REVIEW Completed
07/05/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2012.
07/05/2018 MARTIN BROWN FIRE REVIEW Approved
07/05/2018 GPERU1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
07/19/2018 QJONES1 APPROVAL SHELF Completed
07/19/2018 QJONES1 OUT TO CUSTOMER Completed
07/19/2018 QJONES1 REJECT SHELF Completed