Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T18CM05196
Parcel: 14002010A

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T18CM05196
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2018 MARTIN BROWN FIRE REVIEW Reqs Change Indicate if this structure is considered an enclosed or nonenclosed parking garage per IBC. This will determine sprinkler requirement.
07/20/2018 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change PLUMBING – COMMERCIAL
There is a mop sink on all floor plans located at the northeast corner of Equipment Storage 4-1. A note on enlarged plan 2/4A2.100 refers to the site plan for continuation of the drain line; however no drain line is shown on any of the submitted site plans. Also there is no specification for this fixture on sheet 4P00.001 nor is there a water line to it on Plumbing Floor Plan A, sheet AP02.001.A.
07/20/2018 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change ELECTRICAL – COMMERCIAL
Provide interior lighting watt calculations per 2012 IECC C405.5.2. Per Table C405.5.2(1) the power allowance for parking garages is 0.3 watts per square foot.
Are the specified open bay light fixtures full-cutoff type? The 2012 City of Tucson/Pima County Outdoor Lighting Code does not count full cutoff lumens located under canopy or roof area in the total allowable outdoor lumen count. If the light fixtures are unshielded type as defined in the OLC provide outdoor lighting lumen calculations per one of the commercial options available in OLC Table 401.1 using the “developed area,” also defined in the OLC, for this project as basis for lumen calculations. Ref. 2012 OLC 401.2.1(3).
07/20/2018 FRODRIG2 WATER REVIEW Approved
07/20/2018 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Approved
07/20/2018 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Approved
07/31/2018 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T18CM05196 - New Building #4 (Truck Depot Parking - TEP) Related to DP18-0088
Building Plan Review (1st Review) Tucson Electric Power
3950 E Irvington Road - Zoning is PAD 34 / per Rezoning Case C9-18-03

TRANSMITTAL DATE: July 31, 2018

DUE DATE: August 7, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. COMMENT: Zoning has reviewed the building plans for compliance with the approved version of the development package. While the building footprint is consistent with the DP as it relates to the zoning review purview (Building footprint, Height, square footage, site conditions etc) zoning cannot approve the building plans until the building plans have been approved by the 2nd Party Commercial Plans Reviewers.

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and compare the building plan footprint, building height, and square footage and location to ensure consistency with the DP.

3. COMMENT: If any changes are necessary, due to the 2nd Party Commercial Plan Reviewer's comments that affect or change the building footprint, height, or square footage, the DP will need to be updated prior to approval of the building plans by Zoning.

4. COMMENT: Once the plans have been reviewed and approved by the 2nd Party Commercial Plan Reviewers and zoning has verified consistency with the DP, the building plans can be approved by zoning.

5. COMMENT: Label the height of the north wall on the elevation and cross section drawings. The maximum height proposed and approved on the DP is 19 feet.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: building plans
07/31/2018 JOHN VAN WINKLE ENGINEERING REVIEW Reqs Change T18CM05196

1) Engineering has reviewed the building plans and they appear to be in conformance with the approved DP. Engineering cannot approve the plans at this time as they are still in 3rd party commercial review
2) Engineering can conduct an over the counter review/approval once any outstanding review comments have been addressed and a new work flow opened. Call or Email to schedule

John Van Winkle, P.E.
John.VanWinkle@tucsonaz.gov
520-837-5007
09/20/2018 SVALENZ1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/20/2018 SVALENZ1 OUT TO CUSTOMER Completed