Permit Number: T18CM05195
Parcel: 14002010A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM05195
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/04/2019 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
01/04/2019 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
01/04/2019 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The north, west, and south walls and the roof are listed as "other"; provide the supporting documentation for the proposed U-values (see footnote b on the envelope compliance certificate). Coordinate the wall and roof descriptions with the sections shown on sheet 3A5.001. [Third comment: Envelope compliance calculations were not found in this submittal.] [Second comment: Comment not addressed.] [Initial comment: Demonstrate energy code compliance for the building envelope using calculations based on the current code. Reference: Sections C101.3, C101.5, C103.2, C303, and C401.2, International Energy Conservation Code 2012.]