| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/05/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 10/05/2018 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 10/10/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/16/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. The quantity of exterior luminaires shown in the lumen calcs does not correlate with the exterior luminaires shown on the building. Please clarify or indicate how the Outdoor Lighting Code requirements for this entire TEP project are calculated. Because these buildings are permitted separately but are on the same parcel, the overall site for the project exterior lighting may need to be submitted to get the whole picture. Please advise. 2012 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code |
| 10/17/2018 | DAVID RIVERA | ZONING | REVIEW | Approved |